The most expensive occupancy sensor problem in an office is rarely “the sensor doesn’t work.” It’s the moment it works exactly as configured yet still makes people feel foolish, interrupted, or embarrassed.
A conference room is a good example of how this goes sideways. In a Fremont, CA suite, a room passed every quick walkthrough: someone walked in, waved, walked out, and the lights behaved. Then the suite went live. The lights dropped mid‑meeting—during a budget review chaired by a CFO, with outside auditors in the room. The sensor wasn’t “bad,” but the commissioning target was wrong. The system needed to protect a still, seated meeting with high social stakes.
The standard instinct after a lights‑out complaint is to reach for sensitivity. That’s the trap. In that same layout, the moment you push sensitivity up, a glass sidelight next to a 36‑inch door becomes a motion antenna for corridor traffic. The room stops timing out, but now it turns on randomly when someone walks past the glass. People call it “haunted” and stop trusting the retrofit.
A workable suite doesn’t come from hero tuning. It comes from a small set of profiles by room type, applied consistently, with a few exceptions that are documented like they matter—because they do.
One more translation that saves time: the ticket that says “lights flicker” in a private office is often not a driver issue. In the hybrid‑work era, plenty of complaints that sound like LED problems are just timeouts and “stillness misses.” If a person faces a monitor at a 24‑inch‑deep desk and barely moves for two minutes, PIR will do what PIR does unless the profile is built for that behavior.
Before Settings: A 10‑Minute PIR Reality Check
No setting fixes a sensor that can’t see the zone that matters. In a small office suite, the fastest commissioning wins usually come from walking the room and noticing what the sensor is “staring at” versus what the occupants actually do.
Ψάχνετε για λύσεις εξοικονόμησης ενέργειας με ενεργοποίηση κίνησης;
Επικοινωνήστε μαζί μας για πλήρεις αισθητήρες κίνησης PIR, προϊόντα εξοικονόμησης ενέργειας με ενεργοποίηση κίνησης, διακόπτες με αισθητήρα κίνησης και εμπορικές λύσεις Occupancy/Vacancy.
The sightline check isn’t mystical. Stand under the sensor and trace the likely detection zone. Then look for the recurring offenders: a supply vent blowing across the sensor field, a doorway that frames corridor motion, a glass office front that turns hallway traffic into false triggers, a warm copier changing the room’s background, or partitions blocking the movement that actually happens.
Restrooms are the clearest reminder that placement is not decorative. A two‑stall restroom in San Jose, CA had a sensor centered above the stalls because it looked symmetrical. It also produced the worst possible failure mode: lights going out while someone was still in a stall. This escalated to HR and a demand to disable sensors until re‑commissioned. The repair wasn’t a clever setting; it required moving coverage toward the entry zone and assigning a conservative timeout so stillness wasn’t punished. That fix required patch/paint and a ceiling tile swap, but it was still cheaper than the reputational damage.
Coverage varies across installs. Mounting height, lens pattern, and room geometry change the real detection pattern enough that commissioning cannot be done from a desk. A minimum checklist to prevent “mystery” behavior looks like this:
- Identify cross‑traffic sources: Glass sidelights, open doors, corridor adjacency.
- Identify airflow or thermal oddities: Supply vents, sun patches, warm equipment.
- Identify where people are still: Καθίσματα συνεδρίου, γραφεία, θάλαμοι τουαλέτας.
- Αποφασίστε την πρώτη κίνηση: Είναι στόχος/μάσκα/μετακίνηση και όχι αλλαγές παραμέτρων; Οι ρυθμίσεις είναι δευτεροβάθμιες μέχρι η φυσική εγκατάσταση να είναι λογική.
Τρία Προφίλ που Συνήθως Επιβιώνουν σε Πραγματικά Γραφεία
Μια σουίτα με δέκα διαφορετικές συμπεριφορές κατανομής δεν χρειάζεται δέκα διαφορετικές διαμορφώσεις. Χρειάζεται έναν μικρό αριθμό προφίλ που ένας μελλοντικός υπεύθυνος εγκαταστάσεων μπορεί να κατανοήσει γρήγορα, και ένας τεχνικός επιθεώρησης μπορεί να επαναφέρει χωρίς να κάνει εικασίες.
Οι συνήθειες τεκμηρίωσης έχουν σημασία εδώ επειδή οι μικρές σουίτες γραφείων αλλάζουν: οι ενοικιαστές αλλάζουν, τα έπιπλα μετακινούνται, και το άτομο που «γνωρίζει τις ρυθμίσεις» φεύγει. Ένας πλήρης φάκελος κλεισίματος μπορεί να υπάρχει σε έναν φάκελο SharePoint με όνομα TI_2022_Lighting και να παραμένει λειτουργικά αόρατος. Αυτό που επιβιώνει είναι ένας χάρτης «Τύπος Δωματίου → Προφίλ» μιας σελίδας που προωθείται σε μια συζήτηση email, ή κολλημένος μέσα στην πόρτα του πίνακα φωτισμού αν η πολιτική το επιτρέπει.
Αυτά τα προφίλ είναι στόχοι συμπεριφοράς, όχι καθολικές συνταγές DIP διακοπτών Rayzeek, επειδή τα μοντέλα και το υλικολογισμικό διαφέρουν (DIP τράπεζες έναντι παραμέτρων εφαρμογής). Μετατρέψτε αυτούς τους στόχους στις ακριβείς επιλογές στο εγχειρίδιο εγκατάστασης για το μοντέλο στον οροφή.
Προφίλ Α: «Άτομα Εργάζονται Εδώ» (ανεκτικότητα στη σιωπή)
Αυτή είναι η προεπιλογή για ιδιωτικά γραφεία και αίθουσες συνεδριάσεων, εκτός αν υπάρχει ισχυρός λόγος να τα αντιμετωπίζουμε διαφορετικά. Η υπόθεση είναι απλή: ένα άτομο μπορεί να είναι παρών και παραγωγικό με πολύ λίγη κίνηση. Το χρονικό όριο πρέπει να είναι αρκετά μεγάλο ώστε να αντέξει μια καθιστή συνάντηση ή μια μακρά βιντεοκλήση, και η ανίχνευση πρέπει να δίνει προτεραιότητα στην καθιστή ζώνη, όχι στην πόρτα.
Χτίστε αυτό το προφίλ γύρω από τον κίνδυνο σιωπής. Στα ιδιωτικά γραφεία, η στάση «Zoom σιωπή» είναι πραγματική: κοιτάζοντας μια οθόνη, χέρια στο γραφείο, ελάχιστη κίνηση για λεπτά κάθε φορά. Αν ο αισθητήρας είναι προσανατολισμένος στην πόρτα αντί για την καρέκλα — ή αν το γραφείο έχει γυάλινο πλαϊνό παράθυρο και η πόρτα συχνά μένει ελαφρώς ανοιχτή — η πειρασμός είναι να αυξήσετε την ευαισθησία μέχρι να ανιχνευθεί μικρο-κίνησης. Αυτό συχνά μετατρέπεται σε διαρροή στον διάδρομο και τυχαία ενεργοποιήσεις.
Ένα πιο ασφαλές μοτίβο: βεβαιωθείτε ότι ο αισθητήρας μπορεί να «δεί» την ζώνη της καρέκλας, επεκτείνετε το χρονικό όριο για να καλύψει το παράθυρο σιωπής, και μόνο εξετάστε αλλαγές ευαισθησίας αν ο στόχος και η διαρροή είναι ήδη υπό έλεγχο.
Οι αίθουσες συνεδριάσεων αξίζουν μια σημείωση επειδή το κόστος αποτυχίας τους είναι δυσανάλογο. Το περιστατικό Fremont — φώτα που πέφτουν στη μέση μιας συνάντησης με στελέχη και ελεγκτές — δεν λύθηκε με την αύξηση της ευαισθησίας της ανίχνευσης. Λύθηκε αναγνωρίζοντας τον ρόλο του δωματίου: προστασία των συναντήσεων. Αυτό συνήθως σημαίνει μεγαλύτερο χρονικό όριο από τη υπόλοιπη σουίτα, plus ένα επίπεδο ευαισθησίας που αγνοεί τη φασαρία του διαδρόμου μέσω ενός γυάλινου πλαϊνού παραθύρου. Ένα δωμάτιο συνεδριάσεων που ενεργοποιείται όταν κάποιος περνάει από το γυαλί δεν είναι «πιο προηγμένο». Αισθάνεται απρόβλεπτο.
Profile B: “Dignity Settings” (restrooms and HR-sensitive spaces)
Restrooms are not a place to be clever. The rule that tends to reduce complaint risk is blunt: restrooms get longer timeouts and forgiving behavior, even if the energy manager wants to treat them as easy savings.
The reason is social, not technical. In the San Jose two‑stall case, one lights‑out event in a stall became a story that spread and forced an emergency re‑commissioning. The energy penalty from a longer restroom timeout is usually small compared to the cost of disabling sensors entirely after a backlash. This profile also has a placement bias: avoid coverage blocked by 7‑foot stall partitions, avoid centering over stalls “for symmetry,” and prioritize coverage near the entry and the movement patterns people actually make.
If someone searches for “bathroom sensor embarrassing” or “restroom occupancy sensor keeps turning off,” the correction isn’t a lecture about PIR. The correction is treating the restroom as a high‑stakes human space, commissioning it conservatively, and validating it with an honest stillness test.
Profile C: “Burst Rooms and Transit” (copy rooms, storage, corridors)
This is where aggressive energy savings can be done with less social risk—provided cross‑traffic bleed is managed first. Copy rooms, storage rooms, and corridors are usually “enter, do a short task, exit.” They aren’t designed for stillness. A shorter timeout is often appropriate, but only after the sensor stops triggering on the wrong people in the wrong place.
A Portland, OR copy room shows the common failure mode. The door was routinely propped open with a wedge during busy periods, and the sensor had a sightline to hallway motion through that opening. People complained the copy room was “always on,” and the first proposed fix was to shorten the timeout. That would have made the room worse during real use: people print, wait, collate, and stand relatively still for short stretches. The effective fix was to stop the hallway bleed (aim/masking and door behavior), then set a timeout that turns the room off quickly after a true exit without punishing the 60–120 seconds of print wait.
Corridors add the after‑hours layer. In an Oakland, CA suite, corridor lights were repeatedly on early in the morning. The cleaning crew had a predictable 6–9 pm window and a loop pattern: trash, wipe, move on, repeat. With generous timeouts and glass office fronts, intermittent motion kept re‑triggering the corridor. The tenant didn’t report it as a “comfort complaint” at first; it showed up as an energy optics problem when utility bills were compared month‑over‑month. In transit spaces, shorter timeouts and tighter control of bleed are usually a safer place to be aggressive than in desks, meetings, or restrooms.
Exceptions (kept small on purpose)
Exceptions should be earned and documented, not improvised. A server room with infrequent entry might want a different behavior. A copy room next to a high‑traffic corridor might need masking that other rooms don’t. The rule that keeps suites maintainable is: keep exceptions few, write down why they exist, and keep a rollback path to the profile baseline.
A suite that “works” today but cannot be explained six months later will get reset to defaults by the next person under pressure. Profiles are a defense against that.
The Knobs That Matter (and the Order to Touch Them)
Most commissioning thrash happens because changes are made out of order. To reduce callbacks, follow this sequence: sightline/aim/masking first, timeout second, sensitivity third, and mode policy (occupancy vs. vacancy) as a deliberate decision rather than a patch.
Ίσως ενδιαφέρεστε για
Timeout is the primary lever because it maps directly to the most common complaint: “lights went off while I was still here.” In offices and conference rooms, longer timeouts aren’t laziness; they are a stability choice. The energy savings are preserved by pushing aggressiveness into corridors, storage, and other transit spaces where the stillness window is short and the embarrassment cost is low.
Sensitivity is the most misunderstood lever because it behaves like a trade. In a Sacramento law office suite, a partner’s office went dark while they were reading; the quick fix was to make the sensor “more sensitive.” Then the office started turning on every time someone walked past the glass front in the corridor. The suite didn’t become more comfortable; it became unpredictable. The repair involved backing sensitivity off, aiming toward the seated zone, and extending the timeout modestly. That order matters: when cross‑traffic exists, sensitivity increases amplify the wrong motion as much as the right motion.
Rayzeek devices vary in how these options are represented—DIP switches on the ceiling unit in some installs, app parameters in others. The target is the same: choose a timeout range that matches the room’s stillness risk, and treat sensitivity as a careful adjustment after the detection zone is aimed where it should be. Use the manual for the exact model as a crosswalk, but keep the profile intent stable.
Commissioning Rituals: Test Like the Suite Will Be Used
A “walk in and wave” test produces false confidence. The failure modes show up when people behave normally: seated and quiet, partially hidden by partitions, or moving in short bursts.
The stillness test is a simple example. In a private office, sit in the chair facing the monitor with hands on the desk for two minutes. If the lights fail that test, the next move is not automatically sensitivity. Confirm the sensor sees the seated zone, then adjust the timeout to cover a realistic stillness window. Many tickets logged as “flicker/off” in the hybrid‑work era are resolved by this exact validation, without replacing LEDs or drivers.
Restrooms deserve their own validation ritual because of the dignity cost. If access is possible, a stall stillness test—quiet, minimal movement—should be part of commissioning, especially in small two‑stall restrooms with partitions around 7 feet. A restroom profile that fails this test isn’t “close enough.” The risk is too high. Fix placement/coverage first and timeout second.
Conference rooms get a meeting posture test. The room should survive seated stillness during a real or simulated meeting. If the room only stays on when someone is gesturing, it will fail at the worst moment. And if sensitivity changes make it trigger from hallway motion through a glass sidelight, the room will feel random even when it is technically consistent.
A short checklist that ties tests to fixes prevents random adjustments:
- Run a doorway bleed test (stand near the doorway and observe false triggers from corridor motion).
- Run a stillness test where people actually sit.
- Observe after-hours behavior once during the cleaning window if “all night burn” is a concern.
- Change one variable at a time and document it.
Stop Cranking Sensitivity: A Mini Red‑Team and Rebuild
The obvious fix—”make it more sensitive”—is responsible for a lot of the offices that end up feeling unreliable.
Εμπνευστείτε από τα χαρτοφυλάκια αισθητήρων κίνησης Rayzeek.
Δεν βρίσκετε αυτό που θέλετε; Μην ανησυχείτε. Υπάρχουν πάντα εναλλακτικοί τρόποι για να λύσετε τα προβλήματά σας. Ίσως ένα από τα χαρτοφυλάκια μας μπορεί να σας βοηθήσει.
In glass-front suites, increasing sensitivity doesn’t just detect smaller movements; it detects more wrong movements. Corridor foot traffic, doorways left ajar for airflow, and glass sidelights create exactly the conditions where “more” becomes “random.” That randomness is what occupants remember.
The rebuild is boring on purpose. If a private office goes dark, check whether the sensor is aimed at the chair zone or the doorway zone. Next, increase the timeout to cover still work. Only then, if the suite has controlled cross‑traffic and a sane sightline, consider sensitivity adjustments in small steps. The conference room that failed a CFO meeting didn’t need a heroic sensitivity change; it needed a profile that treated meetings as sacred and a sightline that didn’t watch the hallway.
A safe sequence for change control: confirm bleed sources, change one setting, retest with a stillness or burst-use test, and stop when the socially costly failure mode is prevented. Don’t keep tuning to chase theoretical savings while creating a complaint machine.
Complaint Translation: What They Say vs. What It Means
Occupant complaints are rarely phrased as “timeout is too short” or “field of view includes corridor motion.” They arrive as symptoms. Commissioning gets easier when those symptoms are translated into likely root causes before anyone touches settings.
A practical translation mindset also prevents unnecessary replacements.
- “I had to wave like an idiot during a call” usually points to a stillness miss in a private office or conference room: timeout too short, or sensor can’t see the seated zone.
- “The room is always on” often points to cross‑traffic bleed: door propped open with a wedge, glass-front corridor motion, or an aim issue.
- “Lights flicker” may be a timeout event or partial-off behavior that looks like flicker to a non-technical reporter; confirm with a stillness test before blaming LEDs or drivers.
There is a boundary here. If the suite continues to behave erratically after sightlines are corrected and profile-based settings are validated, it is time to escalate to electrical troubleshooting. Remote advice shouldn’t pretend to diagnose drivers, neutrals, or wiring faults from a complaint log. The translation job is to reduce thrash and route the problem to the right kind of fix.
Once a complaint is translated and resolved, write that translation down in the same place the profiles live. That is how a suite avoids repeating the same debate every time a new person inherits it.
Make It Survive: Documentation, Reset Paths, and Week‑1 Stabilization
A commissioning job isn’t done when the lights “seem fine.” It is done when the settings can survive the next tweak, the next tenant change, or the next urgent email from someone important.
The minimum survivable documentation is small but specific: label the sensor or room type, record which profile it uses, and capture the settings state in a way that can be restored. Photos of DIP switch banks saved into the closeout folder are more useful than a narrative paragraph describing them. A one‑page “Room Type → Profile” map—stored in a shared drive or, where permitted, taped inside the lighting panel door—beats a 60‑page binder that no one opens. Some sites prefer a CMMS entry; that’s fine as long as the mapping is easy to find during a complaint call.
A practical handoff checklist looks like this:
- Write the three profile intents in plain language.
- Note any exceptions and why they exist.
- Include a reset-to-baseline instruction.
- Assign ownership of changes (who is allowed to adjust settings, and who needs to be notified).
That ownership step sounds administrative, but it prevents the “random walk” problem where well-meaning people keep adjusting knobs until the suite is inconsistent.
Compliance constraints vary by jurisdiction and project type, so commissioning advice shouldn’t drift into disabling required controls. The safer framing is: tune within policy. If local requirements impose shutoff behavior, treat the remaining degrees of freedom—placement, aim, timeouts by room type, and documentation—as the levers to make the suite livable.
Finally, allow for a short stabilization window. Week‑1 feedback catches the failure modes that commissioning can miss when the suite is empty. Week‑4 follow‑up catches the “cleaning sweep” and “doors propped open” patterns that only appear once operations settle. That small investment is often cheaper than living with callbacks and eroded trust for the life of the suite.